James Hardie Wet Area Construction Application Guide
The official James Hardie application guide for wet area construction, showing how Villaboard Lining, Secura Flooring, Panel Compressed Sheet and Ceramic Tile Underlay are used to meet NCC and AS 3740 waterproofing rules in bathrooms, showers and laundries. It covers suitable substrates, wall flashings, enclosed and unenclosed showers, baths and basins, and floor and wall penetrations. Read it on this page or download the PDF.
What this covers
- Suitable Wet Area Substrates
- Compliance & AS 3740
- Wall Flashing & Junctions
- Enclosed & Unenclosed Showers
- Baths, Basins & Tubs
- Floor & Wall Penetrations
Applies to HardiePanel Compressed Sheet, Ceramic Tile Underlay, Scyon Secura Flooring and Villaboard Lining.
Key things to remember
The essentials from this guide, at a glance.
- Wet area construction must comply with the National Construction Code 2022 and AS 3740:2021 for waterproofing of domestic wet areas.
- Shower walls are waterproofed or water resistant to a minimum height of 1800mm above finished floor level.
- Walls in general wet areas are waterproofed to 150mm above the finished tile level of the floor.
- An unenclosed shower area extends in an arc 1500mm from the shower connection at the wall.
- Using Secura Flooring or Panel Compressed Sheet means full floor waterproofing is not required outside the enclosed shower area, unless a floor waste is specified.
- Internal tiled corners in non-shower areas use a 6mm gap filled with flexible wet area sealant, and plasterer's angle must not be used.